Alstom cuts gas use by more than a third at London train depots with hard-wired heating interlocks

November 28, 2026
3 mins read
Interior of London Underground Golders Green Depot with a Northern line 1995 Stock train over a maintenance pit.
A Northern line 1995 Stock train rests over an inspection pit inside London Underground's Golders Green Depot. By linking depot access doors directly to heating controls, Alstom cut winter natural gas use by around a third at Golders Green and 37% at Morden. [Photo source: Matt Buck | License: CC BY-SA 4.0]
Alstom Cuts Gas Use by More Than a Third at London Train Depots With Hard-Wired Heating Interlocks Alstom cuts gas use at two London Underground depots by more than a third using hard-wired door interlocks. Every time a large depot door rolls open, warm air escapes and cold air rushes in. Heating that keeps running through that gap wastes gas and money. A hard-wired interlock has now cut recorded gas use at two London depots by more than a third, according to Alstom. Alstom has reported that hard-wired door interlocks cut recorded natural gas use at two London Underground depots, Golders Green and Morden. At Golders Green, recorded winter gas use was about 30% below the 2022/23 baseline in 2024/25 and about 33% below it in 2025/26. At Morden, recorded gas use in its first winter after installation was about 37% below the 2022/23 baseline, falling from 1.99 GWh to 1.26 GWh. Across the winter periods measured at both sites, recorded gas use was about 3.24 GWh below the 2022/23 baselines, which Alstom equates to around 657 tonnes of CO2e in lower associated emissions. Alstom published its announcement on 20 November 2026, and Railway-News reported it on 23 November 2026. Alstom press release · Alstom PDF For building managers, the Alstom results suggest that a controls change can come before any major building upgrade. Check whether your heating keeps running when large doors are open. If it does, ask whether a hard-wired link to the large doors is a practical retrofit. Alstom’s depots are historic maintenance buildings about 180 metres long, with high ceilings and large access doors that open regularly, including in the coldest months. Owners of buildings with loading bays, workshops or vehicle doors may see a similar heat-loss pattern; that is our inference. UK depot charging grants supporting zero-emission fleet infrastructure

How the Controls Work

The fix is a purpose-built, hard-wired interlock. An interlock is a link that stops one system while another condition is active. Here, the heating switches off as soon as the large train-access doors open and resumes only once they are fully closed. Alstom says the system was designed with depot teams and includes controlled overrides that allow it to adapt to changing operational needs. The system was fitted to depots already in operation: Golders Green’s was installed in early 2024, and Morden’s was introduced in 2025. UK First of a Kind rail innovation awards The Golders Green figures show a steady trend. Both figures are winter results against the 2022/23 baseline, and they suggest the savings held up in the second winter. Morden recorded the largest reduction, at about 37%, in its first winter after installation. Dividing the reported figures gives a simple ratio. Around 657 tonnes of CO2e over 3.24 GWh works out to roughly 0.2 kg of CO2e per kWh. This calculation is ours, not a figure Alstom reported. Warehouses, bus depots and workshops with large doors may show a similar pattern, though the Alstom figures do not cover them. The savings come from London sites, so local results will depend on climate, heating systems and how often doors open. That point is our inference. Alstom-built electric trains doubling commuter seating capacity In the latest figures, Alstom reports that hard-wired door interlocks cut recorded gas use by more than a third at two London Underground depots. Across the measured winter periods, the reduction was about 3.24 GWh of natural gas, equal to around 657 tonnes of lower CO2e emissions. Alstom describes the system as purpose-built and fitted to existing historic depot buildings. Owners of large-door buildings can start by checking whether their heating already responds to door status.

Rahul Somvanshi

Rahul, possessing a profound background in the creative industry, illuminates the unspoken, often confronting revelations and unpleasant subjects, navigating their complexities with a discerning eye. He perpetually questions, explores, and unveils the multifaceted impacts of change and transformation in our global landscape. As an experienced filmmaker and writer, he intricately delves into the realms of sustainability, design, flora and fauna, health, science and technology, mobility, and space, ceaselessly investigating the practical applications and transformative potentials of burgeoning developments.

Leave a Reply

Your email address will not be published.

Close-up photograph of a blooming chrysanthemum flower head and foliage
Previous Story

Canada Proposes Deregulating Chrysanthemum White Rust After U.S. Shift

Latest from Energy

Don't Miss